| | Input: Current up to 20 mA, Voltage from 75 mV - 20 V, RTD (Pt100, Pt500, Pt10000, Ni100), TC (J, K, R, S, T, B, E, N), Potentiometer, Rheostat Output: Current (0-20, 4-20 mA), Voltage
|
Datasheet
Manual
Z-Line Flyer
|
|
Power Supply: Consumption: Isolation: Input Protection: Output/Supply Protection: DIP Switch Configuration:
Software Configuration: Status Indicators: Operating Temperature: Humidity: Memory: CE Norms:
| 9 to 40 VDC, 19 to 28 VAC Max 2.5 W; 1.6 W @ 24 VDC (20 mA Output) 1.5 kVAC @ 3 Way Against pulse overvoltages 400 W/ms Against pulse overvoltages 400 W/ms Input type, start-end, output mode (zero elevation, scale inversion), output type (mA, V) Start-end scale, root extraction, burn-out, etc. Power Supply, Out Scale, Error, Alarm -10 to +60 °C Min 30%, max 90% at 40 °C non-condensing EEPROM for all setup data; retention time: 40 years EN 61000-6-4 / 2002, EN 61000-2-2 / 2005, EN 61010-1
|
|
|
Voltage Input:
Current Input: RTD Input:
TC Input:
Potentiometer Input:
Rheostat Input: Strobe Input: Sample Frequency: Response Time:
| 9 Bipolar Scales from 75 mV to 20 V, Input Impedance 1 MOhm, Max resolution 15 bit + sign Bipolar scales up to 20 mA, Input Impedance 50 Ohm, Max resolution 1 μA Pt100, Pt500, Pt1000, Ni100, KTY81, KTY84, and NTC. 3 or 4 wire connctions, excitation current 0.65 mA, resolutions 0.1 °C, RTD or cable interruption automatic detection. Resistive value for NTC: < kOhm. KTY81, KTY84, and NTC settable only by software TC: J, K, R, S, T, B, E, N resolution: 2.5 μV, TC interruption automatic detection, input impedance > 5 MOhm Excitation voltage 300 mV, Input Impedance > 5 MOhm, potentiometer range from 500 Ohm to 10 kOhm (with parallel resistor 500 Ohm) End scale min 500 Ohm, Max 25 kOhm Alternative to relay output 240 sps (11 bit + sign)..15 sps (15 bit + sign) 35 ms (11 bit + sign)..140 ms (15 bit + sign)
|
|
|
Current Output: Voltage Output: Relay Output:
Resolution: Output Retransmission:
| Scales: 0-20/4-20 mA, max load resistance: 600 Ohm Scales: 0-5/0-10/1-5/2-10 V, min load resistance: 2 kOhm Alterantive to strobe input NC relay contact, NO in case of alarm 2.5 μA / 1.25 mV Isolated analog output, current/voltage output Supplied active output connected to passive inputs
|
|
|