HOMECONTACTNEWSPRODUCTSSUPPORTSALES
Like UsFollow UsConnect With Us
PRODUCTS

Compact Converters & IsolatorsModular Converters & IsolatorsTwo-Wire TransmittersI/O Systems (ModBUS & CANopen)Remote Telemetry UnitsCommunication InterfacesHMIs & DisplaysSoftware
PRODUCT SEARCH

  

HELPFUL LINKS

Software DownloadsDatasheets & ManualsRequest a QuoteAbout Us

Z109REG2 - High Performance Universal Converter
Z109REG2
Input: Current up to 20 mA, Voltage from 75 mV - 20 V, RTD (Pt100, Pt500, Pt10000, Ni100), TC (J, K, R, S, T, B, E, N), Potentiometer, Rheostat
Output: Current (0-20, 4-20 mA), Voltage


Datasheet

Manual

Z-Line Flyer



Product Information

Power Supply:
Consumption:
Isolation:
Input Protection:
Output/Supply Protection:
DIP Switch Configuration:

Software Configuration:
Status Indicators:
Operating Temperature:
Humidity:
Memory:
CE Norms:

9 to 40 VDC, 19 to 28 VAC
Max 2.5 W; 1.6 W @ 24 VDC (20 mA Output)
1.5 kVAC @ 3 Way
Against pulse overvoltages 400 W/ms
Against pulse overvoltages 400 W/ms
Input type, start-end, output mode (zero elevation, scale inversion), output type (mA, V)
Start-end scale, root extraction, burn-out, etc.
Power Supply, Out Scale, Error, Alarm
-10 to +60 °C
Min 30%, max 90% at 40 °C non-condensing
EEPROM for all setup data; retention time: 40 years
EN 61000-6-4 / 2002, EN 61000-2-2 / 2005, EN 61010-1
Input

Voltage Input:

Current Input:
RTD Input:



TC Input:

Potentiometer Input:

Rheostat Input:
Strobe Input:
Sample Frequency:
Response Time:

9 Bipolar Scales from 75 mV to 20 V, Input Impedance 1 MOhm, Max resolution 15 bit + sign
Bipolar scales up to 20 mA, Input Impedance 50 Ohm, Max resolution 1 μA
Pt100, Pt500, Pt1000, Ni100, KTY81, KTY84, and NTC. 3 or 4 wire connctions, excitation current 0.65 mA, resolutions 0.1 °C, RTD or cable interruption automatic detection. Resistive value for NTC: < kOhm. KTY81, KTY84, and NTC settable only by software
TC: J, K, R, S, T, B, E, N resolution: 2.5 μV, TC interruption automatic detection, input impedance > 5 MOhm
Excitation voltage 300 mV, Input Impedance > 5 MOhm, potentiometer range from 500 Ohm to 10 kOhm (with parallel resistor 500 Ohm)
End scale min 500 Ohm, Max 25 kOhm
Alternative to relay output
240 sps (11 bit + sign)..15 sps (15 bit + sign)
35 ms (11 bit + sign)..140 ms (15 bit + sign)
Output

Current Output:
Voltage Output:
Relay Output:

Resolution:
Output Retransmission:


Scales: 0-20/4-20 mA, max load resistance: 600 Ohm
Scales: 0-5/0-10/1-5/2-10 V, min load resistance: 2 kOhm
Alterantive to strobe input
NC relay contact, NO in case of alarm
2.5 μA / 1.25 mV
Isolated analog output, current/voltage output
Supplied active output connected to passive inputs
© COPYRIGHT 2016 SENECA INSTRUMENTS, INC. ALL RIGHTS RESERVED